Products
Product Categories
HKD series reactor
Features:
When there are a large number of rectifiers, converter devices and other harmonic sources in the low-voltage power grid, high-order harmonics will seriously endanger the main transformer and the safe operation of electrical equipment. After the reactor and capacitor are connected in series, they can effectively suppress harmonics and improve power quality;
The filter reactor is divided into three-phase and single-phase two types, both of which are iron core dry type. The iron core is made of imported cold-rolled oriented silicon steel sheet with high quality and low consumption. The core column is divided into multiple uniform sections by multiple air gaps. The air gap is epoxy Laminated glass cloth sheets are used as gaps to ensure that the reactance air gap does not change during operation;
The reactor is wound with H-grade enameled wire, and the arrangement is tight and even;
The reactor has a very high withstand voltage level, the reactor can operate safely and without noise at high temperature;
This series reactor has higher quality factor and lower temperature rise, and has better filtering effect;
The external dimensions of this series of reactors refer to the cabinet size design, small size and convenient wiring;
Temperature control includes normally open and normally closed two ways, customized according to customer needs.
Product model:
Compensation method |
Product number |
Reactance rate(%) |
Compensation capacity(kVar) |
Voltage level(V) |
Three-phase compensation |
HKD-0.45/20S7 |
7 |
20 |
450 |
HKD-0.45/30S7 |
7 |
30 |
450 |
|
HKD-0.45/40S7 |
7 |
40 |
450 |
|
Single-phase split complement |
HKD-0.25/3*5F7 |
7 |
3*5 |
250 |
HKD-0.25/3*10F7 |
7 |
3*10 |
250 |
|
HKD-0.25/3*15F7 |
7 |
3*15 |
250 |
Note: The specific dimensions are related to the reactance material and capacity of the product. If you have special requirements when purchasing, please confirm with our company.
Technical Parameters:
Working power (system voltage) |
400V / 660V / 1140V etc. |
Reactor type |
6%/7%/12%/14% (customizable) |
Reactor temperature rise |
Iron core does not exceed 80K, coil temperature rise does not exceed 90K |
Pressure level |
3kV/min |
Linearity of reactance value |
The difference between the inductance value at 1.8 times the power frequency rated current and the rated reactance value does not exceed -5% |
Any two-phase reactance value |
The difference is not more than ± 3% |
Insulation class |
Class F |
Overload capacity |
Less than or equal to 1.3 5 times the rated current continuous operation |
Noise |
<48dB |
Contact us
Address: Building 3, Xingsha International Enterprise Center, Changsha Economic and Technological Development Zone
Phone:0731-85524209
Email:cshk@cshkdq.com