MFC911 Series Microcomputer Integrated Protection Measurement and Control Device
Key words:
Classification:
MFC911 Series Microcomputer Integrated Protection Measurement and Control Device
Hotline:
Email:
Detailed introduction
MFC911 Series Basic Integrated Protection Australian I Control Device
| Device Model |
Protection function |
measurement and control function |
Use |
| MFC911C-I Microcomputer current type protection device |
1. Three-stage overcurrent protection2Overload protection 3. Non-power protection 4. Zero-sequence overcurrent protection |
Three-phase protection current, zero-sequence current,8Road entry detection,2Road alarm output, cumulative record of events and protection events, operating state alarm output, "Threeremote communication |
For incoming or feeder |
| MFC911C-U Microcomputer voltage type protection device |
1. Zero-sequence overvoltage protection 2. Undervoltage protection 3. Overvoltage protection |
Zero sequence voltage, three-phase bus voltage,8Road entry detection,2Road alarm output, cumulative record of events and protection events, operating state alarm output, "Threeremote communication |
For10kVClass voltage transformer cabinet |
| MFC911C-Lmicrocomputer line protection device |
1. Two-stage overcurrent protection 2. current inverse time protection 3. Reclosing and Post Acceleration 4. Low voltage load shedding 5. Zero-sequence overcurrent protection 6. Zero-sequence overvoltage protection |
Three-phase protection current, zero sequence current (calculation),A,CPhase measured current, three-phase bus voltage,8Road entry detection,2Road alarm output, cumulative record of events and protection events, operating state alarm output |
For general incoming or feeder |
| MFC911C-T Microcomputer with transformer protection device |
1. Two-stage overcurrent protection 2. current inverse time protection 3. Overload protection 4. Non-power protection 5. Zero-sequence overcurrent protection 6. Zero-sequence overvoltage protection |
Three-phase protection current, zero sequence current (calculation),A,CPhase measured current, three-phase bus voltage,8Road entry detection,2Road alarm output, cumulative record of events and protection events, operating state alarm output |
Applicable10kVGrade medium and small capacity with transformer |
| MFC911C-P microcomputer busPTmeasurement and control device |
1. Grounding protection 2. PTSwitching protection |
Three-phase bus voltage,8Road entry detection,2 Road alarm output, cumulative record of events and protection events, operating state alarm output |
ForPTSwitch andPTmeasurement and control |
| Optional Description:C—Modbus-RS485Communication F--Anti-jump and operation circuit (AC type device only includes operation circuit, excluding anti-jump) E—External zero sequence current (protection device without external measurement current) |
|||
| Selection case:MFC911C-LCF,Line protection,RS485Communication, including anti-jump and operation loop MFC911C-LECF,Line protection,RS485Communication, including anti-jump and operation circuit, with external zero-sequence current, cancel measuring currentMFC911C-T,With transformer protection device,RS485Communication, without anti-jump and operation loop |
|||
| Special Note: Only one of circuit breaker and microcomputer protection device can have anti-jumping function. If both have anti-jumping function, it will affect the normal opening and closing of circuit breaker.MFC911C-I, MFC911C-UFor economic products, only optional communication, no other optional functions. |
|||
MFC911 Series Standard Integrated Protection Measurement and Control Device
| Device Model |
Protection function |
measurement and control function |
Use |
| MFC911-Lmicrocomputer line protection device |
1. Two-stage overcurrent protection 2. current inverse time protection 3. Reclosing and Post Acceleration 4. Low voltage load shedding 5. Zero-sequence overcurrent protection 6. Zero-sequence overvoltage protection |
Three-phase protection current, zero sequence current (calculation),A,CPhase measured current, three-phase bus voltage,8Road entry detection,2Road alarm output, cumulative record of events and protection events, operating state alarm output |
For general incoming or feeder |
| MFC911-T Microcomputer with transformer protection device |
1. Two-stage overcurrent protection 2. current inverse time protection 3. Overload protection 4. Non-power protection 5. Zero-sequence overcurrent protection 6. Zero-sequence overvoltage protection |
Three-phase protection current, zero sequence current (calculation),A,CPhase measured current, three-phase bus voltage,8Road entry detection,2Road alarm output, cumulative record of events and protection events, operating state alarm output |
Applicable10kVGrade medium and small capacity with transformer |
| MFC911-P microcomputer busPTmeasurement and control device |
1. Grounding protection 2. PTSwitching protection |
Three-phase bus voltage,8Road entry detection,2 Road alarm output, cumulative record of events and protection events, operating state alarm output |
ForPTSwitch andPTmeasurement and control |
| MFC911-B Microcomputer standby power supply self-switching device |
1. Incoming line/bus joint standby 2. Single-phase two-stage overcurrent protection (incoming cabinet) |
Single-phase protection current, three-phase bus voltage,8Road entry detection,2Road alarm output, cumulative record of events and protection events. |
For standby power self-switching |
| MFC911-M1 Microcomputer motor integrated protection device |
1. Two-stage overcurrent protection 2. Low voltage load shedding 3. Overload protection 4. Negative sequence overcurrent protection 5. Overheat protection 5. Zero-sequence overcurrent protection 6. Zero-sequence overvoltage protection |
Three-phase protection current, zero sequence current (calculation),A,CPhase measured current, three-phase bus voltage,8Road entry detection,2Road alarm output, cumulative record of events and protection events, operating state alarm output |
For small and medium capacity motors |
| MFC911-M2 Microcomputer motor differential protection device |
1. Differential quick break 2. ratio differential 3. CTBreak lock |
Three-phase protection current, opposite side differential current,8 Road entry detection,2Road alarm output, control circuit disconnection alarm |
withMFC911-M1Use together to complete the protection of large-capacity motors |
| MFC911-C microcomputer capacitor protection device |
1. Two-stage overcurrent protection 2. current inverse time protection 3. Low voltage load shedding protection 4. automatic casting and cutting 5. Overvoltage protection 6. Zero-sequence overcurrent protection 7. Zero-sequence overvoltage protection |
Three-phase protection current, zero sequence current (calculation),A,CPhase measured current, three-phase bus voltage,8Road entry detection,2Road alarm output, cumulative record of events and protection events, operating state alarm output |
Used for parallel small and medium capacity capacitors |
| Optional Description:C—Modbus-RS485Communication F1Anti-jump and operation circuit (AC type device only includes operation circuit, excluding anti-jump)E—External zero sequence current (protection device without external measurement current) |
|||
| Selection case:MFC911-LCF,Line protection,RS485Communication, including anti-jump and operation loop MFC911-LECF,Line protection,RS485Communication, including anti-jump and operation circuit, with external zero-sequence current, cancel measuring currentMFC911-T,With transformer protection device,RS485Communication, without anti-jump and operation loop |
|||
| Special Note: Only one of circuit breaker and microcomputer protection device can have anti-jumping function. If both have anti-jumping function, it will affect the normal opening and closing of circuit breaker. |
|||